Here's the Know-How

Providing real-time information to building occupants

The term mass notification originated with the Unified Facilities Criteria (UFC) document 4-021-01, titled Design and O&M: Mass Notification Systems, created by the Department of Defense (DoD). The UFC outlines the design, operation and maintenance of mass notification systems (MNSs) required on all DoD properties, including posts for the Air Force, Army, Marine Corps and Navy.

The UFC defines mass notification as “the capability to provide real-time information to all building occupants or personnel in the immediate vicinity of a building during emergency situations. To reduce the risk of mass casualties, there must be a timely means to notify building occupants of threats and what should be done in response to those threats. Pre-recorded and live-voice emergency messages are required by this UFC to provide this capability.”

The UFC recommends the use of a combined fire alarm and mass notification system, particularly in new construction of military facilities, where the building fire alarm control panel forms a single combined system that performs both functions. For smaller buildings, the public address system may also integrate with this combined system, provided the PA system can be supervised for integrity.

Codes and Components
Initially seen as a solution for the military, MNSs are gaining popularity outside the armed forces. The 2010 edition of NFPA 72: National Fire Alarm & Signaling Code’s lengthy Chapter 24 outlines requirements for the design and installation of emergency communication systems within commercial facilities. While recent events such as the Virginia Tech campus shootings and severe weather incidents have raised demand for emergency communication systems for commercial properties, the new NFPA codes have begun to set a precedent of using fire alarm systems to support the added duties of a supervised and more survivable ECS.

So that MNSs serve as more than a common fire alarm voice evacuation system, NFPA 72 requires that “security personnel should be able to effect message initiation over the MNS from either a central control station or alternate (backup) control station. Where clusters of facilities exist, one or more regional control stations might also exercise control.” It also requires the MNS to offer a “dynamic library of scripted responses to various emergency events that would be easily customizable to meet the needs of the individual customer.”

To service this need, distributed messaging units, commonly referred to as local operator consoles (LOCs), are typically tied to the fire alarm/ECS network and installed throughout a facility or campus to provide authorized users a means systems such as e-mail or reverse-911 systems offer alternative methods for alerting occupants. However, these technologies are not supervised for faults or breaks, nor do they encompass a more “survivable” design that would enable the ongoing delivery of accurate communications even if one or more parts of the system’s network were down. Likewise, there are no codes or standards in existence that require these systems to be regularly tested and maintained to a specific level of performance.

NFPA 72 makes clear that distributed recipient notification systems such as text messaging or e-mail shall not be used in lieu of required audible and visual alerting emergency communication systems. This is due to the possibility of delivering conflicting information such as a text message directing a person to remain in place while the fire alarm system in the building provides the evacuation message. If the fire alarm evacuation system is activated before the occupants receive the message, there could be confusion.

For the same reason, NFPA 72 requires that a building’s fire alarm and emergency communication systems be integrated and programmed to allow all ECS functions to supersede the fire alarm. This priority setting avoids the situation of a fire alarm evacuating a building while a message to “shelter in place” is sent through the same facility’s ECS.

Today, a layered approach using a fire alarm/ECS and an integrated distributed recipient notification system is considered the best solution for reaching the largest number of occupants. However, the sequence of notifications -- from all systems -- must be considered, and any potential delays in the transmission of communications must be minimized.

For these reasons, all systems should be integrated and coordinated with a facility’s emergency plan.

In the middle of an emergency, flashing strobes accompanied by live or pre-recorded audible instructions tend to have a much higher effect on occupants.

At the same time, highly visual signs in large areas of assembly can offer information specific to the emergency or display a simple message such as “evacuate.” To deliver voice instructions to those outside, large speaker clusters can be installed on the exterior of a building or throughout a campus.

Using a combination of audible and visual notification devices, such as strobes, voice communications (indoor speakers and outdoor Giant Voice variety speakers) and programmable LED signage is considered the most intrusive solution for capturing the attention of occupants and delivering a clear, audible message.

For multiple buildings or campuses spread across a city, state or even the globe, some fire alarm manufacturers such as NOTIFIER have harnessed VoIP technology to deliver live voice messages to anywhere in the world via the Internet. These state-of-the-art systems include one or more workstations from which security or facilities personnel can send emergency communications via VoIP.

Fire alarm system manufacturers and installers work within a tightly regulated industry, which was the first to create requirements for the design and installation of ECS for commercial properties. The marriage of ECS and fire alarm control systems is a growing trend that is expected to continue reaching into larger varieties of facilities and multi-building properties, including K-12 schools, high-rise buildings, mass transit hubs and even public gathering places such as theaters, restaurants and places of worship.

This article originally appeared in the September 2011 issue of Security Today.

Featured

  • Maximizing Your Security Budget This Year

    Perimeter Security Standards for Multi-Site Businesses

    When you run or own a business that has multiple locations, it is important to set clear perimeter security standards. By doing this, it allows you to assess and mitigate any potential threats or risks at each site or location efficiently and effectively. Read Now

  • ISC West 2024 is a Rousing Success

    The 2024 ISC West security tradeshow marked a pivotal moment in the industry, showcasing cutting-edge technology and innovative solutions to address evolving security challenges. Exhibitors left the event with a profound sense of satisfaction, as they witnessed a high level of engagement from attendees and forged valuable connections with potential clients and partners. Read Now

    • Industry Events
    • ISC West
  • Live From ISC West: Day 2

    What a great show ISC West 2024 has been so far. The second day on Thursday was as busy or even more hectic than the first. Remember to keep tabs on our Live From ISC West page for news and updates from the show floor at the Sands Expo, because there’s more news coming out than anyone could be expected to keep track of. Read Now

    • Industry Events
    • ISC West
  • A Unique Perspective on ISC West 2024

    Navigating a tradeshow post-knee surgery can be quite the endeavor, but utilizing an electric scooter adds an interesting twist to the experience. While it may initially feel like a limitation, it actually provides a unique perspective on traversing through the bustling crowds and expansive exhibition halls. Read Now

    • Industry Events
    • ISC West

Featured Cybersecurity

New Products

  • EasyGate SPT and SPD

    EasyGate SPT SPD

    Security solutions do not have to be ordinary, let alone unattractive. Having renewed their best-selling speed gates, Cominfo has once again demonstrated their Art of Security philosophy in practice — and confirmed their position as an industry-leading manufacturers of premium speed gates and turnstiles. 3

  • AC Nio

    AC Nio

    Aiphone, a leading international manufacturer of intercom, access control, and emergency communication products, has introduced the AC Nio, its access control management software, an important addition to its new line of access control solutions. 3

  • A8V MIND

    A8V MIND

    Hexagon’s Geosystems presents a portable version of its Accur8vision detection system. A rugged all-in-one solution, the A8V MIND (Mobile Intrusion Detection) is designed to provide flexible protection of critical outdoor infrastructure and objects. Hexagon’s Accur8vision is a volumetric detection system that employs LiDAR technology to safeguard entire areas. Whenever it detects movement in a specified zone, it automatically differentiates a threat from a nonthreat, and immediately notifies security staff if necessary. Person detection is carried out within a radius of 80 meters from this device. Connected remotely via a portable computer device, it enables remote surveillance and does not depend on security staff patrolling the area. 3